Characteristics of Micrologic Electronic Trip Units (2024)

Characteristics of Micrologic Electronic Trip Units

Introduction

Micrologic electronic trip units provide the following functions:

oProtection of the electrical distribution or specific applications

oMeasurement of instantaneous values and measurement of average values (demand) for electrical quantities

oKilowatt hour metering

oOperational assistance such as peak demand, customized alarms, and operation counters

oCommunication

Identification

Identify the trip unit installed on the circuit breaker by using the fourcharacters on the front face:

Characteristics of Micrologic Electronic Trip Units (1)

Protection (X)

Case (Y)

Measurements (Z)

Application (T)

Characteristics of Micrologic Electronic Trip Units (2)

Characteristics of Micrologic Electronic Trip Units (3)

Characteristics of Micrologic Electronic Trip Units (4)

Characteristics of Micrologic Electronic Trip Units (5)

1

2

4

5

6

7

SI

LS0I

LS0IR

LSI

LSIG

LSIR

2

3

CompactNSX 100/160/250

CompactNSX 400/630

A

E

No measurement

Ammeter

Energy

G

AB

M

Z

AL

Distribution

Generator

Subscriber

Motor

16Hz2/3

Alarm

Examples

Micrologic1.3

SI

400 or 630A

Distribution

Micrologic2.2G

LS0I

100, 160 or 250A

Generator

Micrologic2.3

LS0I

400 or 630A

Distribution

Micrologic 2.3M

LS0I

400 or 630A

Motor

Micrologic4.2

LS0IR

100, 160 or 250A

Distribution including trip on earth leakage

Micrologic4.3AL

LS0I

400 or 570A

Distribution including alarm on earth leakage

Micrologic 5.2A

LSI

100, 160 or 250A

Ammeter

Distribution

Micrologic 5.3E

LSI

400 or 630A

Energy

Distribution

Micrologic 6.3E-M

LSIG

400 or 630A

Energy

Motor

Micrologic 7.2E-AL

LSI

100, 160 or 250A

Energy

Distribution including alarm on earth leakage

Micrologic 7.3E

LSIR

400 or 630A

Energy

Distribution including trip on earth leakage

Type of protection:

IInstantaneous

LLong-time

S0Short-time (time delay cannot be adjusted)

SShort-time

GGround-fault

R Residual (earth-leakage)

Micrologic Trip Unit Families

The range of Micrologic trip units is made up of several families:

oMicrologic1, 2, and 4 without display screen

oMicrologic5, 6, and 7 with display screen.

On Micrologic1, 2, and 4 trip units, the protection functions are set using adjustment dials on the front face of the trip unit:

Characteristics of Micrologic Electronic Trip Units (6)

On Micrologic5, 6, and 7 trip units, the protection functions are set:

oBy using the adjustment dials

oBy additional settings on the keypad. Setting values are displayed on the screen

oThrough EcoStruxure Power Commission software.

Characteristics of Micrologic Electronic Trip Units (7)

For more information about the Micrologic5, 6, and 7 trip units, refer to DOCA0141EN, CompactNSX Micrologic5/6/7 Electronic Trip Units - User Guide.

In Rating of Micrologic Trip Units

The In rating (in amps) of a Micrologic trip unit corresponds to the maximum value of the long-time protection (Ir) setting range for the trip unit. The setting range is indicated on the label on the front face of the trip unit (this label is visible on the front face of the CompactNSX circuit breaker after the trip unit has been fitted).

Characteristics of Micrologic Electronic Trip Units (8)

Example: Micrologic 5.2A 250 trip unit:

oSetting range: 100-250A

oIn rating = 250A

Distribution Trip Unit

The following figure and table define the protection functions for distribution-type Micrologic trip units.

Micrologic5 and 6

Characteristics of Micrologic Electronic Trip Units (9)

Micrologic7

Characteristics of Micrologic Electronic Trip Units (10)

Item

Parameter

Description

Micrologic(1)

2

4

5

6

7

A

Trip unit setting range: minimum setting/maximum setting.

The trip unit rating In corresponds to the maximum value of the Ir setting range.

O

O

O

O

O

B

Ir

Long-time protection pickup

L

C

tr

Long-time protection time delay

O

O

D

Isd

Short-time protection pickup

S

E

tsd

Short-time protection time delay

O

O

F

I2t ON/OFF

Short-time protection I2t curve in ON or OFF position

G

Ii

Instantaneous protection pickup

I

O

O

H

Ig

Ground-fault protection pickup

G

I

tg

Ground-fault protection time delay

J

I2t ON/OFF

Ground-fault protection I2t curve in ON or OFF position

K

IΔn

Earth-leakage protection pickup

R

L

Δt

Earth-leakage protection time delay

(1)Functions:

✓: Adjustable

O: Fixed

–: Not present

Thermal Memory

The thermal memory is used to simulate temperature build-up and cooling in conductors caused by current variations, according to a time constant. In the event of an overload, the trip units with a thermal memory memorize the build-up temperature caused by the current. Memorizing the build-up temperature leads to a reduction in the trip time.

All Micrologic trip units incorporate a thermal memory as standard:

oFor Micrologic2 and 4 trip units, the time constant is 15minutes.

oFor Micrologic5, 6, and 7 trip units, the time constant is 20minutes.

Motor Trip Units

The following figure and table define the protection functions for Micrologic typeM trip units.

Characteristics of Micrologic Electronic Trip Units (11)

Item

Parameter

Description

Micrologic typeM

1.3

2

6E

A

Trip unit setting range: minimum setting/maximum setting.

The trip unit rating In corresponds to the maximum value of the setting range.

O

O

O

B

Ir

Long-time protection pickup

L

C

Class

Long-time protection trip class

D

Isd

Short-time protection pickup

S

E

tsd

Short-time protection time delay

O

O

O

F

Ii

Instantaneous protection pickup

I

O

O

O

G

Ig

Ground-fault protection pickup

G

H

tg

Ground-fault protection time delay

Iunbal

Phase-unbalance protection pickup

Characteristics of Micrologic Electronic Trip Units (12)

O

tunbal

Phase-unbalance protection time delay

O

(1) Functions:

✓: Adjustable

O: Fixed

– : Not present

Motor Trip Unit: Additional Protection

Micrologic typeM trip units (in particular Micrologic6E-M) also incorporate additional protection for the motor application. For more information, refer to DOCA0141EN, CompactNSX Micrologic5/6/7 Electronic Trip Units - User Guide.

Indication LEDs

Indication LEDs on the front of the trip unit indicate its operational state.

The LEDs and their meaning depend on the type of Micrologic trip unit.

Type of Micrologic trip unit

Description

Distribution

Characteristics of Micrologic Electronic Trip Units (13)

oReady LED (green): Blinks slowly when the electronic trip unit is ready to provide protection.

oOverload pre-alarm LED (orange): Shows a steady light when the load exceeds 90% of the Ir setting.

oOverload alarm LED (red): Shows a steady light when the load exceeds 105% of the Ir setting.

Motor

Characteristics of Micrologic Electronic Trip Units (14)

oReady LED (green): Blinks slowly when the electronic trip unit is ready to provide protection.

oOverload temperature alarm LED (red): Shows a steady light when the motor thermal image exceeds 95% of the Ir setting.

The Micrologic1.3M trip unit, which provides short-time protection only, displays the Ready LED (green).

The indication LEDs function for circuit breaker load currents:

oAbove 15A on a Micrologic trip unit rated 40A

oAbove 30A on Micrologic trip units rated >40A

The limit value is indicated on the front panel, above the Ready LED of the Micrologic trip unit.

NOTE: For the Micrologic 4 and 7 trip units, the protection functions are supplied by a second power supply, in addition to the current transformer supply. The Ready LED blinks irrespective of the load, indicating that the standard protection functions are operational.

To activate the Ready LED when the load current is below the limit value, you can:

oInstall a 24Vdc external power supply module which allows the trip unit to be monitored continuously, even when the circuit breaker is open. For more information, refer to Compact NSX&NSXm Catalogue.

oOr, during maintenance visits, connect the pocket battery to monitor the trip unit.

NOTE: If the pre-alarm and alarm LEDs keep lighting up, perform load shedding to avoid tripping due to a circuit breaker overload.

Test Port

Micrologic trip units come with a test port specifically for testing trip unit operation.

Characteristics of Micrologic Electronic Trip Units (15)

This port is designed for:

oConnecting the pocket battery for local Micrologic testing

oConnecting the USB maintenance interface for testing, setting the Micrologic trip unit, or for installation diagnostics

Interchangeability of Micrologic Trip Units

Onsite replacement of trip units is simple:

oNo connections to make

oNo special tools (for example, calibrated torque wrench)

oCompatibility of trip units provided by mechanical cap

oTorque limited screw provides correct torque

Characteristics of Micrologic Electronic Trip Units (16)

The simplicity of the replacement process means that it is easy to make the necessary adjustments as operation and maintenance processes evolve.

NOTE: The screw head is accessible when the trip unit is installed, so the trip unit can still be removed.

NOTE: On the CompactNSX with R, HB1 and HB2 breaking performances the trip units are not interchangeable.

Sealing the Protection

Seal the transparent cover on Micrologic trip units to prevent modification of the protection.

Characteristics of Micrologic Electronic Trip Units (17)

On Micrologic5, 6, and 7 trip units, it is possible to use the keypad, with the cover sealed, to read the protection settings and measurements.

Characteristics of Micrologic Electronic Trip Units (2024)
Top Articles
Latest Posts
Recommended Articles
Article information

Author: Ms. Lucile Johns

Last Updated:

Views: 6267

Rating: 4 / 5 (41 voted)

Reviews: 88% of readers found this page helpful

Author information

Name: Ms. Lucile Johns

Birthday: 1999-11-16

Address: Suite 237 56046 Walsh Coves, West Enid, VT 46557

Phone: +59115435987187

Job: Education Supervisor

Hobby: Genealogy, Stone skipping, Skydiving, Nordic skating, Couponing, Coloring, Gardening

Introduction: My name is Ms. Lucile Johns, I am a successful, friendly, friendly, homely, adventurous, handsome, delightful person who loves writing and wants to share my knowledge and understanding with you.